Copper · 120 volt · amps and watts

Extension Cord
Amp Chart

A long cord does not fail by catching fire. It fails by arriving weak. Every number here is the most a cord of that gauge and length can carry while still delivering usable voltage at the far end, in amps or in watts.

Supply
120 V
Conductor
Stranded copper
Resistance at
75 °C / 167 °F
Watts
Amps × 120 V
Gauges
18 to 2 AWG
Range
25 to 250 ft
01

Size a cord

Set the run and the load. The answer is the smallest cord that keeps the sag under 3%, which is the number to use for anything with a motor in it.

1070130190250
60 W1500 W3000 W4500 W6000 W
Or start from a tool
12AWG

02

Motors and tools

The most a cord can carry at a 3% drop, the tight standard. Use this for anything that spins or compresses: saws, drills, pumps, compressors, refrigerators, pressure washers. These loads pull hard on startup and overheat when the voltage sags. Switch the table between amps and watts.

Less load More load ° marks a cell held back by the wire’s own heat rating, not by the length.
03

Heat and light

The same cords at a 5% drop, the looser standard most printed cord charts use. It is fine for loads that only make heat or light and do not care about a slightly soft supply: heaters, kettles, work lights, chargers, string lights. Do not use this table for a motor.

04

How far a wattage reaches

Appliances are labeled in watts, so read this one from the nameplate. Find your wattage down the side and the answer is the longest run that gauge can serve at a 3% drop. A 1500 W heater on a 12 gauge cord reaches 70 feet; on 16 gauge it will not run at all, at any length.

Longest run in feet at a 3% drop
Shorter run Longer run A dash means the load is past that cord’s own rating, so no length is short enough.
05

Which cord to buy

The same rule, read backwards. Find your load down the side, your run across the top, and buy that gauge or heavier. Remember that gauge numbers run backwards: 10 AWG is thicker than 14 AWG.

Minimum gauge at a 3% drop
06

Field notes

Watts, volts, amps

Watts divided by 120 gives amps, which is what the wire actually feels. A 1500 W heater is a 12.5 A load; a 15 A saw is an 1800 W load. Every watt figure here assumes a nominal 120 volts.

Low voltage is the danger

At 250 ft a 16 AWG cord pulling 10 A will not melt. It will deliver about 93 volts. A motor fed 93 volts draws extra current to make up the difference, runs hot, and dies young. The cord survives; the tool does not.

Never run it coiled

Every rating here assumes the cord is laid out flat. Left wound on a reel, a loaded cord traps its own heat and can run 20 to 30 °C hotter. If you cannot uncoil it, drop to the next heavier gauge.

Two cords are one cord

Fifty feet plus fifty feet is a 100 ft run in this chart, with two extra connections that heat up and pull apart. Add the lengths, then look up the total.

Read the jacket

The gauge is printed every few feet: 12 AWG 3/C SJTW means 12 gauge, three conductors, thermoplastic jacket, W for wet locations. Trust the print over the packaging.

240 volts doubles it

Percent drop scales with voltage, so the same cord on a 240 V circuit carries twice the amps, and four times the watts, at the same percentage. Welders and RV feeds get far more reach for the copper.

Startup is the hard part

A compressor or pump can pull three to six times its running watts for the first second. That surge is what a long thin cord turns into a stall, so size for the motor, not for the label.

Where cord stops being cord

4 and 2 gauge exist as welding cable and generator feeder, not as something with a molded 15 A plug on the end. Once the chart sends you there you are building a temporary feeder, which is a different job with different rules.

Copper only

These figures are copper. Cheap copper-clad aluminum cords need roughly two gauge sizes heavier for the same job. If a 100 ft 12 gauge cord feels suspiciously light, it probably is.